MAMM‐WHSP‐IOM‐1HP5A(October2011) 4
manually reset by interrupting power or by
removing the call for mechanical heating or
cooling. Intelligent reset automatically
terminates the lockout mode 5 minutes after a
lockout condition occurs. The purpose of
intelligent reset is to allow the unit to attempt to
reset itself if the condition that caused the
original lockout corrects itself. After 3 attempts in
a 6000 second (100 minute) period after the first
lockout, the intelligent reset feature is terminated
and the unit stays in lockout until the unit is
manually reset. The number of reset attempts is
limited to protect the unit from severe damage.
UNOCCUPIED (NIGHT SETBACK AND/OR
NIGHT SETUP) MODE: This mode is functional
with the auto changeover with night setback wall
thermostat and the auto changeover with night
setback/setup and override wall thermostat only.
The unoccupied mode allows the space to be
controlled at different settings. The unoccupied
mode can be activated in two ways:
By closing the circuit between terminals
"COM" and "NS" via a field supplied switch
or time clock contacts (see Figure 1).
By supplying 24 volts to terminals "COM"
and "NS".
In the unoccupied mode, the controller ignores
the normal fan and compressor signals from the
wall thermostat and only accepts a call for
compressor operation from the night
setback/setback portion of the wall thermostat.
The signal at terminals "COM" and "NS" can be
"daisy-chained” between many units. When the
signal to terminals "COM" and “NS” is removed,
the random start timing function is activated.
NIGHT SETBACK/SETUP INPUT FROM THE
THERMOSTAT:
Once the unoccupied mode is activated and the
occupied mode operation of the fan and
compressor are terminated, the controller can
only activate compressor operation from the wall
thermostat at terminal "3" (see Figure 2). Night
setback compressor operation occurs if the
space temperature falls to 12°F below the
occupied heating set point or if the space
temperature rises to 8°F above the occupied
cooling set point. The fan will automatically
operate and cycle with the compressor due to
the fan interlock feature.
OVERRIDE: The override feature is available
with the wall thermostat and is activated by the
push button on the face of the wall thermostat
(see Figure 3). When pushed, the unit will switch
back to its normal occupied temperature set
points on the wall thermostat for 2 hours. After 2
hours, the unit will resume its unoccupied mode
operation until the unoccupied mode signal is
removed from terminals "COM" and "NS". The
push button is only operable when the unit is in
the unoccupied mode.
EMERGENCY SHUTDOWN MODE: Emergency
shutdown allows the unit to be made inoperable
via a remote signal. The emergency shutdown
mode can be activated in two ways:
By closing the circuit between terminals
"COM" and "ESD" via a field supplied set of
contacts (see Figure 4).
By supplying 24 volts to terminals "COM"
and "ESD".
In shutdown mode, the reversing valve, fan and
compressor are inoperable, the lockout alarm
circuits are activated and the green LED flashes
repeatedly 2 times (quick ON and one long
OFF). The unit does not need to be reset. The
signal at terminals "COM" and "ESD" can be
"daisy-chained" between many units. When the
signal to terminals "COM" and "ESO" is
removed, the random start timing function is
activated.
AUXILIARY DRY CONTACTS: A pair of
normally open contacts at terminals "DRC IN"
and "DRC OUT” shall close and a pair of
normally closed contacts at terminals "DRC IN"
and "DRC OUT” shall open when the
compressor is energized. This will allow
connection of 24-volt power to the normally
closed contacts to supply power to a normally
open (powered close) motorized valve when the
compressor is on.
TEST PIN JUMPER: An on-board pair of male
terminals provides for an optional mode of
operation which defeats both forms of
compressor time delays. If a hard-wired jumper
is placed across the "TEST" and "TEST IN"
terminals, the random start time delay and the
compressor's five minutes of anti-short cycle
time delay will be ignored. However, the two,
four and six second time delays on the fan,
reversing valve and compressor remain in place.
LOW PRESSURE BYPASS: The dip switches
labeled “DY1” and “DY2” allow for four different
amounts of low pressure switch bypass: zero,
one, two and 3 minutes. The low pressure
bypass timer logic occurs anytime the board
senses a low pressure switch fault.
Comments to this Manuals